Experimental performance analysis of a packaged R290 refrigeration unit retrofitted with R170 for ultra-low temperature freezing

dc.centroEscuela de Ingenierías Industrialeses_ES
dc.contributor.authorRodríguez-Criado, Juan Carlos
dc.contributor.authorExpósito-Carrillo, José Antonio
dc.contributor.authorPeris-Pérez, Bernardo
dc.contributor.authorDomínguez-Muñoz, Fernando
dc.date.accessioned2025-09-03T08:52:48Z
dc.date.available2025-09-03T08:52:48Z
dc.date.issued2021-11-24
dc.departamentoIngeniería Mecánica, Térmica y de Fluidoses_ES
dc.descriptionhttps://openpolicyfinder.jisc.ac.uk/id/publication/12611es_ES
dc.description.abstractWhile the global refrigeration capacity installed in ultra-low temperature applications is considerably lower than in standard refrigeration, the interest in such systems has risen during the last months due to their emerging demand for the preservation of mRNA vaccines. Several theoretical studies can be found in the literature for ultra-low temperature applications. However, there is still a lack of reliable experimental data that may be used for the models validation and, thereby, to perform more rigorous investigations. In light of this, the present manuscript proposes an ultra-low temperature refrigeration unit based on an indirect cascade system, developed by retrofitting a standard low-temperature R290 packaged unit. In this investigation, firstly, the suitability of the original components is assessed and, then, the unit is experimentally tested within a wide range of operating conditions. Thereby, the system’s reliability is evaluated by assessing different parameters, such as discharge, condensing and evaporating temperatures and performance ratios. The main results showed a successful behaviour at the operating conditions tested, exhibiting a COP that ranged from 0.6 to 1.6 for cold room temperatures between -80 ºC and -65 ºC, respectively.es_ES
dc.identifier.citationInternational Journal of Refrigeration 134 (2022) 105–114es_ES
dc.identifier.doi10.1016/j.ijrefrig.2021.11.015
dc.identifier.urihttps://hdl.handle.net/10630/39739
dc.language.isoenges_ES
dc.publisherElsevieres_ES
dc.rights.accessRightsopen accesses_ES
dc.subjectIngeniería térmicaes_ES
dc.subjectCriogeniaes_ES
dc.subjectHidrocarburoses_ES
dc.subject.otherHydrocarbonses_ES
dc.subject.otherEthanees_ES
dc.subject.otherPropanees_ES
dc.subject.otherRetrofites_ES
dc.subject.otherUltra-low temperaturees_ES
dc.titleExperimental performance analysis of a packaged R290 refrigeration unit retrofitted with R170 for ultra-low temperature freezinges_ES
dc.title.alternativeAnalyse expérimentale des performances d'un groupe frigorifique monobloc au R290 converti au R170 pour la congélation à très basse températurees_ES
dc.typejournal articlees_ES
dc.type.hasVersionAMes_ES
dspace.entity.typePublication
relation.isAuthorOfPublicationa05ef485-824c-489f-9b7b-deedc07a34a9
relation.isAuthorOfPublication13b6551b-f454-4a54-8ef4-e59f1fdbcc58
relation.isAuthorOfPublication.latestForDiscoverya05ef485-824c-489f-9b7b-deedc07a34a9

Files

Original bundle

Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
Pre-Proof.pdf
Size:
1.51 MB
Format:
Adobe Portable Document Format
Description:

Collections